The Accu-CT revenue-grade, split-core current transformer offers outstanding accuracy and one-handed operation.
  • Revenue-Grade Accuracy, Unprecedented Linearity
  • Window Opening 0.75 Inch
  • The Accu-CT revenue grade, split-core current transformer offers outstanding linearity and phase angle accuracy with a unique one-handed opening and closing mechanism.
  • Safe: burden resistor built-in, 333 mVac voltage output at rated full scale current, no shorting blocks needed
  • IEEE C57.13 and IEC 60044-1 accuracy: over full temperature range and down to 1% of rated current
  • Exceptionally low phase angle error: essential for accurate power and energy measurements
  • Glove-friendly: easy to open and install with one hand while wearing safety gloves
  • Approvals: UL recognized, CE mark, RoHS

Environment:
The T-ACT-0750 Sensors are for use in Indoor environments

Measurements:
The T-ACT-0750 Sensors support the following measurements: AC Current, Amps (A)

Accuracy: ±0.75% from 1% to 120% of rated primary current

Phase angle: ±0.5 degrees (30 minutes) from 1% to 120% of rated current

Accuracy standards: IEEE C57.13 class 1.2 and IEC 60044-1 class 1.0

Primary rating: 5 to 250 Amps, 600 Vac, 60 Hz nominal

Salida: 333.33 mVac at rated current (direct compatibility only with H22-001 & sensors S-FS-TRMSAS-FS-TRMSA-D)

Operating temperature: -30°C to 55°C

Safe: integral burden resistor, no shorting block needed, unlessotherwise noted

Standard lead length: 8 ft (2.4 m), 18 AWG

UL recognized, CE mark, RoHS

Assembled in USA: qualified under Buy American provision in ARRA of 2009