AO-BH-50 Gas Control Panel with Touch Screen

Bosean

New

The AO-BH-50 Gas Control Panel features a user-friendly touch screen interface, providing accurate and reliable gas monitoring and control for various industrial applications.

Add to wishlist

The product adopts industrial touch 4.3-inch LCD screen, featuring high stability, high accuracy and high intelligence, and rich external control ports. We provide gas detector OEM/ODM service.

This product is an intelligent controllable system for signal input of 8-channel/16-channel/32-channel (4-20) mA/RS485 transmitter developed by the company. The product adopts industrial touch 4.3 inch / 7 inch LCD screen, featuring high stability, high accuracy and high intelligence. The external control port is rich, users can freely choose the type of plug-in transmitter and access port, and set it easily. On-site inspection and alarms are available. The system has integrated sound and light alarms and provides a relay normally open control terminal.

The system is widely used in applications where toxic and harmful gases need to be detected. When the index of a certain gas to be tested in the field exceeds or falls below the set standard, the system will perform a series of alarm actions, such as alarm, exhaust, tripping, etc.

Detection principle: Collect standard 4~20mA signal input or RS485 communication input (optional), analyze and display the current gas concentration of each channel, and operate related alarm signals, and transmit the information to the computer through RS485 bus.

Applicable objects: The system supports input signals of various standard detectors, such as gas detectors: carbon monoxide, hydrogen sulfide, sulfur dioxide, hydrogen, ammonia, oxygen, chlorine and combustible gases.

Specifications

ProductBH-50-Touch Screen(4.3 inch)
External port 8 roads, 16 roads, 32 roads
Display method 4.3inch/7inch Industrial touch LCD screen
Operating Voltage 220V±10%,50Hz
System power consumption ≦10W
Signal input Two-wire 4~20mA, three-wire 4~20mA or four-wire RS485
Signal output Two-wire RS485 (MODBUS)
Operating temperature -10℃~50℃
Working humidity 0-95%RH (no condensation)
Relay control port Passive relay output, full load power 1kW
Installation method Wall mounting
Dimensions (4.3 inch screen) 380x230x10mm(L*W*H)
Dimensions (7-inch screen) 440x290x10mm(L*W*H)
ModelRangeL-alarmH-alarm
CO 0-1000ppm 35ppm 200ppm
O2 0-30%vol 19.5%vol 23.5%vol
H2 0-100%LEL 20%LEL 50%LEL
H2S 0-100ppm 10ppm 20ppm
CH4 0-100%LEL 20%LEL 50%LEL
C2H4O 0-20ppm 10ppm 15ppm
C2H4 0-100%LEL 20%LEL 50%LEL
C3H8 0-100%LEL 20%LEL 50%LEL
C2H5OH 0-100%LEL 20%LEL 50%LEL
NH3 0-100ppm 25ppm 50ppm
CL2 0-20ppm 5ppm 10ppm
O3 0-20ppm 5ppm 10ppm
SO2 0-100ppm 2ppm 5ppm
PH3 0-20ppm 0.3ppm 5ppm
CO2 0-50000ppm 1000ppm 2000ppm
NO 0-250ppm 20ppm 50ppm
NO2 0-20ppm 5ppm 10ppm
HCN 0-500ppm 10ppm 20ppm
HCL 0-50ppm 10ppm 20ppm
CH2O 0-10ppm 2ppm 5ppm
VOC 0-100ppm 20ppm 50ppm
C6H6 0-100ppm 20ppm 50ppm