New
Quantidade | Preço (Imposto Excluido) |
Desconto % |
---|---|---|
1+ | 420,00 € | 0% |
5+ | 398,92 € | 5.0179% |
15+ | 378,00 € | 10% |
25+ | 357,00 € | 15% |
Availability date:
El Transductor WattNode T-WNB-D permite medidas precisas a un bajo costo para medidas de energía en instalaciones de AC.
It provides accurate measurement at low cost to meet your needs for sub-metering, net-metering, energy management, and performance contracting applications. This WattNode Delta or Wye-connection kWh Transducer works with Magnelab AC Current Transformers and a Pulse Input Adapter to provide True RMS kilowatt hours of energy used, even for loads with non-sinusoidal waveforms. Because these sensors tie directly into the line, they should be used only by qualified personnel. This model supports a 3-phase Delta-connection of 480 VAC.
Referencias para Pedidos:
T-WNB-3D-240 Transductor KWh 3 Fases 'Delta' para 240Vac (Salida Pulsos).
T-WNB-3D-480 Transductor KWh 3 Fases 'Delta' para 480Vac (Salida Pulsos).
T-WNB-3Y-208 Transductor KWh 3 Fases 'Y' para 208/240Vac (Salida Pulsos).
T-WNB-3Y-208-P Transductor KWh 3 Fases 'Y' para 208/240Vac (Opt P3).
The WattNode provides accurate measurement at low cost to meet your needs for sub-metering, net-metering, energy management, and performance contracting applications. This WattNode Delta-connection kWh Transducer works with Magnelab AC Current Transformers and a Pulse Input Adapter to provide True RMS kilowatt hours of energy used, even for loads with non-sinusoidal waveforms. Because these sensors tie directly into the line, they should be used only by qualified personnel. This model supports a 3-phase Delta-connection of 208/240 VAC.
• Measures 1, 2, or 3 phases in 2, 3, or 4 wire configurations.
• Use with wide choice of CTs (sold separately),ratings from 5 to 1500 amps.
• Accurate measurement of 1-,2-, or 3-phase configurations.
• Easy to install and wire.
• Pulse output - Compatible with pulse input logger models.
• Small size - Can be installed in existing service panels or junction boxes.
• Diagnostic LEDs – Confirms proper installation for all phases.
• Bidirectional metering – Net metering for PV (photovoltaic) solar and wind power generation with only one meter.
• Metering of variable frequency drives.
• Line powered - No external supply required.
• Detachable terminal blocks - Easy to install and remove.
• UL, cUL Listed - Designed and tested for safety and use throughout North America.
• CE Mark – Can be installed throughout the EU.
Entorno:
The T-WNB-3D-240 Sensor is for use in Indoor environments
Medidas:
The T-WNB-3D-240 Sensor supports the following measurements: Kilowatt Hours (kWh)
• Mide 1, 2, ó 3 fases en configuración de 2, 3, ó 4 hilos.
Configuración en Delta o 'Y' y rangos: 208, 480 Voltios AC
1 Phase 2 Wire 208V (Sin neutro)
1 Phase 2 Wire 240V (Sin neutro)
1 Phase 3 Wire 120V/240V
3 Phase 3 Wire 208V (Sin neutro)
3 Phase 4 Wire 120V/208V
Rating: FCC Class A
Operating: voltage range: ±20% of nominal
Frequency: 50/60 Hz
Entradas CT : 0-0.5 VAC operating, 3 VAC maximum
Precisión: ±0.45% of reading + 0.05% FS through 25th harmonic
(dependent on CT used and line variation accuracy could be 1.5% to 4% of reading)
Enclosure: high impact, UL rated ABS plastic
Connectors: UL, CSA recognized, detachable screw terminals (14 AWG), 600V
Operating temp range: -30 to 60°C (-22 to 140°F)
Operating humidity range: 0 to 90% RH, non-condensing
Dimensiones: 8.5 cm x 14.3 cm x 3.8 cm (3.3 in. x 5.6 in. x 1.5 in.)
Peso: 295 g (10.4 oz.)