Ningún producto
Estos precios se entienden sin IVA
UPM309RGW
Nuevo
Disponible el:
El Sensor mide: | Corriente AC |
Señal de Salida: | RS485 o Ethernet |
Alimentación: | alimentado de la red AC |
Clasificación IP del Sensor | IP54 (panel frontal); IP20 (terminales) |
Power supply
Voltage range (according to the model): Instrument with RS485 port: 230 VAC ±15% or 115 VAC ±15% on request
Instrument with Ethernet port: 85...265 VAC
Frequency: 50/60 Hz
Voltage inputs
Maximum measurable voltage: 600 VAC max L-L
Minimum voltage for FFT calculation: 20/35 VAC (multiplied by PT ratio in case of PT use) with direct connection
Input impedance: ›1.3 MOhm
Frequency: 45 - 65 Hz
Current inputs
Maximum value: 3 selectable scales, 500/4000/20000A
Minimum current value for FFT calculation: 70 A for FSA 500 A, 400 A for FSA 4000 A, 1500 A for FSA 20000 A
2% harmonic accuracy ±2 digits
Typical accuracy
Voltage: ±0.2% reading in 10% FS...FS range (FS=Full Scale value)
Current: ±0.4% reading in 5% FS...FS range
Power: ±0.5% reading ±0.1% FS (PF=1)
Frequency: ±0.1% reading ±1 digit in 45...65 Hz range
Active energy: Class 1 according to IEC/EN 62053-21
Reactive energy: Class 2 according to IEC/EN 62053-23
Display & keyboard
Display: Backlighted LCD, 78x61 mm
3 rows, 4 digits + symbols
Keyboard: 4 front buttons
Communication ports
Type: RS485 optoisolated or Ethernet
Protocols: MODBUS RTU/ASCII in case of RS485 port
HTTP, NTP, DHCP, MODBUS TCP in case of Ethernet port
Baud rate: 300 a 57600 bps in case of RS485 port
10/100 Mbps in case of Ethernet port
2 DIGITAL OUTPUTS (DO)
Type: NPN or PNP, passive optoisolated
Maximum values (according to IEC/EN 62053-31): 27 VDC - 27 mA
Energy pulse length (only for DO in pulse mode): 50 ±2ms ON time
Max output reaction time (only for DO in alarm mode): 1 s
ANALOG OUTPUT (AO)
Type: Active optoisolated
Selectable ranges: 0...20 / 4...20 mADC
Maximum load: 500 Ω
DIGITAL INPUT (DI)
Type: Optoisolated
Voltage range: 80 ... 265 VCA-CC
Wire diameter for terminals
Measuring terminals (A&V): 2.5 mm2 / 14 AWG
Terminals for I/O, AUX, RS485 port: 1.5 mm2 / 16 AWG
Size & weight
LxHxP, W: 96x96x39 mm, max 310 g
Environmental conditions
Operating temperature: -25°C ... +55°C (3K6)
Storage temperature: -25°C ... +75°C (2K3)
Max humidity (without condensation): 80%
Sinusoidal vibration amplitude: 50 Hz ±0.075 mm
Protection degree - frontal part: IP54 (granted only in case of installation in a cabinet with at least IP54 protection degree)
Protection degree - terminals: IP20
Pollution degree: 2
Installation and use: Internal
Standard compliance (for the parts applicable for instrument)
Directives: 2006/95/EC, 2004/108/EC
Safety: EN 61010-1, EN 61010-2-030
EMC: EN 61326-1, EN 55011, EN 61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-5, EN61000-4-6, EN61000-4-11, EN61000-6-2
Basic | ENH | ||
CURRENT INPUTS | Rogowski inputs (3 MFC150 included) | • | • |
AUXILIARY POWER SUPPLY (make one choice only) |
115 VAC ±15% (only for instrument with RS485 port) | • | • |
230 VAC ±15% (only for instrument with RS485 port) | • | • | |
85...265 VAC (only for instrument with Ethernet port) | • | ||
COMMUNICATION PORT (make one choice only) |
RS485 for MODBUS RTU/ASCII communication | • | • |
Ethernet for HTTP, MODBUS TCP communication | • | ||
INSTRUMENT REMOTE MANAGEMENT | WintoolNET | • | • |
Web server (only for instrument with Ethernet port) | • | ||
SIGN REPRESENTATION IN MODBUS PROTOCOL (make one choice only) |
Sign bit | • | • |
2’s complement | • | • | |
2 DIGITAL OUTPUTS | For alarm events or pulse emissions | • | • |
ANALOG OUTPUT (only for instrument with RS485 port) | 0...20 / 4...20 mADC, programmable | ◦ | |
DIGITAL INPUT | To synchronise the DMD value calculation | • | • |
DMD VALUE CALCULATION MODE | Digital input synchronisation or Fixed window | • | |
Digital input synchronisation, Fixed or Sliding window | • | ||
MEMORY | 1 MB | • | |
8 MB | • | ||
RECORDINGS | Active and reactive power AVG values | • | |
Real time params MIN/AVG/MAX values (up to 24 params programmable) | • | ||
Energy counters | • | ||
WIRING MODES | Three phase, 4 wires, 3 currents (3.4.3) | • | • |
Three phase, 3 wires, 2 currents (3.3.2) | • | • | |
Single phase (1ph) | • | • | |
THD & HARMONICS | Voltage and current THD values | • | • |
Voltage and current harmonics up to 15th | • | ||
APPARENT ENERGY COUNTERS (make one choice only) |
Total counters | • | • |
Separated Inductive&Capacitive counters | • | • |
Legend
• = standard
◦ = optional
430,00 €
1 529,00 €
915,00 €
587,00 €
730,00 €
550,00 €
245,00 €