T-VER-E50B2 HOBO-Veris Power & Energy Meter

T-VER-E50B2

Onset

New

880,00 €

tax excl.

Add to wishlist

The E50B2 Power & Energy Meter combines exceptional performance and easy installation to deliver a cost-effective solution for power and energy monitoring needs. The T-VER-E50B2 can be installed on standard DIN rail or surface mounted as needed. It works with the HOBO UX, U30, ZW, H22 & H21 data loggers.

Features:
  • Measures Power Factor (PF), Reactive Power (VAR), Watt Hours (Wh) and more.
  • Range: 90-600VAC – Wye or Delta configurations
  • Accuracy: ANSI 12.20 0.5% accuracy, IEC 62053-22 Class 0.5S
  • Compatible with CTs from 5 to 32000A (333mV output)
  • Bright backlit LCD
  • UL listed, CE, California CSI Solar, ANSI C12.20
Environment:
The T-VER-E50B2 Sensor is for use in Indoor environments
Measurements:
The T-VER-E50B2 Sensor supports the following measurements : AC Current, AC Voltage, Amp Hour (Ah), Amps (A), Kilowatt Hours (kWh), Kilowatts (kW), Power Factor (PF), Volt-Amp Reactive (VAR), Volt-Amp Reactive Hour (VARh), Volt-Amps (VA), Volts (V), Watt Hours (Wh), Watts (W)
 
Other models available (prices may be different):
E50B1 DIN Energy Meter, VAR Pulse Out
E50C2 DIN Energy Meter, Modbus, Pulse Out
E50C3 DIN Energy Meter, Modbus, Logging, Pulse Out
E50H5 DIN Energy Meter, BACnet, Logging, Pulse In
E51C2 Bi-Directional DIN Energy Meter, Modbus, Pulse Out
E51C3 Bi-Directional DIN Energy Meter, Modbus, Logging, Pulse Out
 

Build better energy efficiency and power management with the E50B2 Power & Energy Meter. This cost-effective sensor is simple to deploy and can either be installed on standard DIN rail or be surface mounted. The E50B2 integrates with HOBO UX, U30, ZW, H22, and H21 data loggers.

  • Measures Power Factor (PF), Reactive Power (VAR), Watt Hours (Wh) and more.
  • Range: 90-600VAC – Wye or Delta configurations
  • Accuracy: ANSI 12.20 0.5% accuracy, IEC 62053-22 Class 0.5S
  • Compatible with CTs from 5 to 32000A (333mV output)
  • Bright backlit LCD
  • UL listed, CE, California CSI Solar, ANSI C12.20

Environment:
The T-VER-E50B2 Sensor is for use in Indoor environments

Measurements:
The T-VER-E50B2 Sensor supports the following measurements:

AC Current, AC Voltage, Amp Hour (Ah), Amps (A), Kilowatt Hours (kWh), Kilowatts (kW)
Measurement Accuracy:  
   Real Power and Energy IEC 62053-22 Class 0.5S, ANSI C12.20 0.5%
   Reactive Power and Energy IEC 62053-23 Class 2, 2%
   Current 0.4% (+0.015% per °C deviation from 25°C) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from 25°C) from 1% to 5% of range
   Voltage 0.4% (+0.015% per °C deviation from 25°C) from 90V (L-N) to 600VAC (LL)
   Sample Rate 2520 samples per second
   Data Update Rate 1 sec
   Type of Measurements True RMS up to the 21st harmonic 60 Hz, One to three phase AC system
Input Voltage Characteristics:  
   Measured AC Voltage Minimum 90VL-N (156VL-L) for stated accuracy
UL Maximums: 600VL-L (347VL-N)
CE Maximums: 300VL-N (520V L-L)
   Metering Over Range +20%
   Impedance 2.5 MΩ (L-N)/5 MΩ (L-L)
   Frequency Range 45 to 65 Hz
Input Current Characteristics:  
   CT Scaling Primary: Adjustable from 5 A to 32,000 A
   Measurement Input Range 0 to 0.333VAC or 0 to 1.0VAC (+20% over-range)
   Impedance 10.6kΩ (1/3 V mode) or 32.1kΩ (1 V mode)
Output:  
   Alarm Contacts N.C., static output (30VAC/DC, 100mA max. @ 25°C, derate 0.56mA per °C above 25°C)
   Real/Reactive Energy
    Pulse Contacts
N.O., static output (30VAC/DC, 100mA max. @ 25°C,
derate 0.56mA per °C above 25°C)
Mechanical Characteristics:  
   Weight 0.62 lb (0.28 kg)
   IP Degree of Protection (IEC 60529) IP40 front display; IP20 Meter
   Display Characteristics Back-lit blue LCD
   Terminal Block Screw Torque 0.37 ft•lb (0.5 N•m) nominal/0.44 ft-lb (0.6 N•m) max
   Terminal Block Wire Size 26 to 14 AWG (0.13 to 2.08 mm2)
   Rail T35 (35mm) DIN Rail per EN50022
Environmental Conditions:  
   Operating Temperature Meter: -30° to 70°C; Display: 0° to 50°C
   Storage Temperature Meter: -40° to 85°C; Display: -10° to 60°C
   Humidity Range <95% RH (non-condensing)
   Altitude of Operation 3 km max.
Metering Category:  
   North America CAT III; for distribution systems up to 347 V L-N/600VAC L-L
   CE CAT III; for distribution systems up to 300 V L-N
   Dielectric Withstand Per UL 508, EN61010
   Conducted and Radiated Emissions FCC part 15 Class B, EN55011/EN61000 Class B (residential and light industrial)
   Conducted and Radiated Immunity EN61000 Class A (heavy industrial)
Safety:  
   North America (cULus) UL508 (open type device)/CSA 22.2 No. 14-05
   Europe (CE) EN61010-1:2001

30 other products in the same category: