New
Data Logger HOBO
Availability date:
Number of Channels | 4 Digital |
ADC Bits | 32 bits |
With Display | No |
IP Classification | Indoor IP50 |
Communications | USB |
Battery Life | 1 year |
Maximum Pulse Rate | 120 Hz |
Memory Capacity | 520,192 or 4,124,672 measurements |
This 4-channel energy data logger UX120 combines the functionality of four separate data loggers into one compact unit. It enables energy management professionals -- from energy auditors to building commissioners -- to easily track building energy consumption, equipment runtimes, and water and gas flow rates.
Simultaneously measures and records pulse signals, events, state changes, and runtimes
Capable of 500,000 measurements (over 4 million with expanded memory version), enabling longer deployments with fewer site visits
Maximum pulse rate – 120 Hz
Pulse input range – 0 to 24VDC
Streamlines deployment via a range of start/stop options, logger status LEDs, and high-speed USB 2.0 data offload
Works with Onset's Energy & Power Meter T-VER-E50B2 to measure Power Factor (PF), Reactive Power (VAR), Watt Hours (Wh) and more.
HOBO 4-Channel Pulse Data Logger Memory Options:
Model UX120-017 with >500,000 Measurement Memory.
Model UX120-017M with >4 Million Measurement Memory.
Supported Measurements (sensors sold separately):
AC Current
AC Voltage
Amp Hour (Ah)
Amps (A)
Event,
Kilowatt Hours (kWh)
Kilowatts (kW),
Motor On/Off
Power Factor (PF), Pulse Input
Run-time
Volt-Amp Reactive (VAR)
Volt-Amp Reactive Hour (VARh)
Volt-Amps (VA)
Volts (V)
Watt Hours (Wh)
Watts (W)
Simultaneously measures and records pulse signals, events, state changes, and runtimes
Stores up to over 500,000 measurements, enabling longer deployments with fewer site visits
Maximum pulse rate – 120 Hz
Pulse input range – 0 to 24VDC
Inputs: | |
External Contact Input: | Electronic solid state switch closure or logic driven digital signals to 24 V |
Maximum Pulse Frequency: | 120 Hz |
Maximum State, Event, Runtime Frequency: | 1 Hz |
Bits: | 4–32 bits depending on pulse rate and logging interval |
Maximum Pulses Per Interval: | 7,863,960 (using maximum logging rate) |
Driven Logic Signal: | Input Low: ≤ 0.4 V; Input High: 3 to 24 V |
Absolute Maximum Rating: | Maximum Voltage: 25 V DC Minimum Voltage: -0.3 V DC |
Solid State Switch Closure: | Input Low: < 10 KΩ; Input High: > 500 KΩ |
Internal Weak Pull-Up: | 100 KΩ |
Input Impedance: | Solid state switch closure: 100 KΩ pull up; Driven signal: 4.5 KΩ |
Minimum Pulse Width: | Contact closure duration: 500 uS; Driven logic signal: 100 uS |
Lockout Time: | 0 to 1 second in 100 ms steps |
Edge Detection: | Falling edge, Schmitt Trigger buffer |
Preferred Switch State: | Normally open or Logic '1' state |
Logging: | |
Resolution: | Pulse: 1 pulse, Runtime: 1 second, State and Event: 1 State or Event |
Logging Rate: | 1 second to 18 hours, 12 minutes, 15 seconds |
Time Accuracy: | ± 1 minute per month at 25°C (77°F) (see Plot A on next page) |
Battery Life: | 1 year, typical with logging intervals greater than 1 minute and normally open contacts |
Memory: | |
Memory | UX120-017: 520,192 measurements (assumes 8-bit) UX120-017M: 4,124,672 measurements (assumes 8-bit) |
Download Type | USB 2.0 interface |
Download Time | 30 seconds for UX120-017, 1.5 minutes for UX120-017M |
Physical: | |
Operating Range | Logging: -40° to 70°C (-40° to 158°F); 0 to 95% RH (non-condensing) Launch/Readout: 0° to 50°C (32° to 122°F) per USB specification |
Weight | 149 g (5.26 oz) |
Size | 11.4 x 6.3 x 3.3 cm (4.5 x 2.5 x 1.3 inches) |
Environmental Rating | IP50 |
139,00 €
139,00 €
279,00 €
139,00 €
318,00 €
449,00 €
1 275,00 €
175,00 €
165,00 €
550,00 €
550,00 €
430,00 €
59,00 €
85,00 €
105,00 €
130,00 €
259,00 €
170,00 €
265,00 €
225,00 €
195,00 €
185,00 €
1 025,00 €
1 025,00 €
625,00 €
625,00 €
625,00 €
769,00 €